PRODUCTS CENTER
Cambodia Double chamber counter current ion exchanger
Category:
Product Description
Double chamber counter current ion exchanger
1. Introduction
1.1. Purpose
Double chamber counter current ion exchanger is used for water purification. During the operation and regeneration of the equipment, the direction of the liquid flow through the exchanger layer is opposite. The weak and strong resins are respectively installed in the two chambers, and the weak and strong resins are used in series to form the desalination system.
1.2. Model meaning
JNSS100•170/80
J -------- ion exchange
N -------- countercurrent regeneration
SS----------double chambers
100 -------- equipment diameter (mm)
170 / 80 --- resin layer height (mm)
1.3. Structural features
1.3.1. The water inlet device is in the form of main pipe and branch pipe.
1.3.2. The strong and weak resins are separated by porous plate and water cap.
1.3.3. The water outlet device is quartz sand cushion and dome shaped porous plate.
1.3.4. The equipment is equipped with local sampling device and inlet and outlet pressure gauges.
1.3.5. The pressure rating of all interface flanges is PN1.0MPa.
1.3.6. The equipment is equipped with manual rubber lined valve or pneumatic rubber lined diaphragm valve.
1.3.7. The height of inert packing layer of equipment shall be considered as 200 mm.
1.3.8. The equipment is lined with 1751 semi-rigid adhesive for anti-corrosion.
1.3.9. The orientation of grease inlet is 315 ° and that of grease unloading port is 330 °.
1.4. Product series
The product series of double chamber counter current ion exchanger is shown in table 21-1.
Table 21-1 main product series of double chamber counter current ion exchanger
| Nominal diameter Resin height (strongly/weakly) Item |
DN1600 | DN2000 | DN2500 | DN2800 | DN3000 |
| 1700/800 | 1000/1500 | 1000/1400 | 600/2000 | 1200/1500 | |
| Model | JNSS160 | JNSS200 | JNSS250 | JNSS280 | JNSS300 |
| 170/80 | 100/150 | 100/140 | 60/200 | 120/150 | |
| Volume of filling layers(m3) | 0.4 | 0.63 | 0.98 | 1.23 | 1.41 |
| Resin volume (m3) | 3.4/1.6 | 3.14/4.71 | 4.9/6.87 | 3.69/12.3 | 8.48/10.60 |
| Quartz sand volume(m3) | 1.24 | 2.15 | 3.15 | 4.41 | 4.95 |
| Capacity(t/h) | 40 | 65 | 100 | 125 | 140 |
| Equipment weight(kg) | 1890 | 4370 | 6760 | 8560 | 10420 |
| Running loading(N) | 136900 | 241900 | 337000 | 478500 | 566800 |
2. Technical parameters
The main technical parameters of double chamber counter current ion exchanger are shown in table 21-2
Table 21-2 main technical parameters of double chamber counter current ion exchanger
| Item | Data | Item | Data |
| Design pressure(MPa) | 0.6 | container form | Vertical |
| Design temperature(℃) | 50 | Welded joint coefficient | 0.85 |
| design flow rate(m/h) | 20 | material of the main body | Q235-B |
| Design capacity(t/h) | see table 21-1 | Resin layer height(mm) | see table 21-1 |
3. Equipment appearance and structural dimensions
The configuration and structural dimensions of double chamber countercurrent ion exchange are shown in Fig. 21-1 and table 21-3

Table 21-3 dimensions of double chamber counter current regeneration ion exchanger
| Nominal diameter Resin layer height Item |
DN1600 | DN2000 | DN2500 | DN2800 | DN3000 | |
| H | 5379 | 5464 | 5595 | 5892 | 6164 | |
| H1 | 237 | 217 | 302 | 302 | 267 | |
| H2 | 560 | 580 | 695 | 695 | 730 | |
| H3 | 883 | 943 | 1088 | 1088 | 1193 | |
| H4 | 1400 | 1450 | 1600 | 1600 | 1850 | |
| ∮ | 1450 | 1800 | 2000 | 2150 | 2275 | |
| L | 1071 | 1293 | 1560 | 1712 | 1847 | |
| L1 | 513 | 583 | 658 | 658 | 803 | |
| L2 | 463 | 483 | 498 | 548 | 633 | |
| N×M | 180×220 | 180×220 | 300×350 | 300×350 | 300×350 | |
| DN1 | 100 | 125 | 150 | 150 | 200 | |
| DN2 | 80 | 80 | 80 | 100 | 125 | |
| DN3 | 40 | 40 | 40 | 40 | 50 | |
| quartz sand cushion | Particle size 1~2 | 200 | 200 | 200 | ||
| Particle size 2~4 | 100 | 150 | 150 | |||
| Particle size 4~8 | 100 | 100 | 100 | |||
| Particle size 8~16 | 100 | 150 | 200 | |||
| Particle size 16~32 | 250 | 250 | 300 | |||
4. Ordering instructions
4.1. The regeneration liquid of the equipment is hydrochloric acid, sulfuric acid and sodium hydroxide. When sulfuric acid is used for regeneration, the order must be specified.
4.2. The height of exchanger layer depends on the water quality, and it must be indicated when ordering.