Excitation system of 600 MW generator set

key word:Heat exchange element


Product description

Excitation system of 600 MW generator set

 

1. Introduction

1.1. Purpose

UNITROL 5000 is the fifth generation excitation regulator of UNITROL series, which is used in static excitation system of synchronous generator (including 300 and 600 MW thermal generator). UNITROL 5000 not only contains the core technology of its former two generation excitation regulators UNITROL F and UNITROL P, but also absorbs the most advanced research achievements and technologies in the field of front digital control, such as DSP digital signal processing technology. UNITROL 5000 system is upgraded from UNITROL F and UNITROL P platform, adding new special solutions and means (such as SCR energy flow bridge dynamic, intelligent current sharing, low residual voltage quick start-up and perfect communication function) and a variety of debugging means (such as windows interface application programming - GAD development engineering tool package, CMT) The ARCnet network technology of UNITROL P has also been transplanted to UNITROL 5000 for serial communication of various parts in excitation system.

1.2. Model meaning

Q5S-O/U251-S6000

Q --- four channels: two months automatic channel and two independent manual channels

5------UNITROL 5000 microcomputer system

S ------ (n-1) redundancy

O ------- no additional functions

U2 -------- converter (bridge) model

5 -------- number of SCR rectifier bridges

1-------Three phase full wave, 1 thyristor per bridge wall

S -------- DC single break circuit breaker

6000--------Rated current of circuit breaker

1.3. Structural features

The static excitation system of 600 MW thermal power generator is composed of the excitation transformer te at the output end of UNITROL 5000, the thyristor rectifier bridge VZ, the magnetic field breaker Q plus the non-linear de excitation resistance Rm (or the AC side breaker), the microcomputer excitation regulator AVR, the excitation diode VD (which can be cancelled by using the AC power supply), and the current limiting resistance R. If AC power source is used, rectifier bridge and rectifier transformer are also included.

The self shunt excitation mode of self excitation system (including excitation starting device) is shown in 29-1.

The excitation transformer te at the generator end is separately installed near the enclosed bus bar at the generator outlet. The primary side is directly connected with the enclosed bus bar, and the secondary side is connected with the AC bus bar cabinet in the excitation cabinet by cable. After controlled rectification, it is connected to the rotor excitation of the generator with sliding ring structure through the de excitation cabinet or DC bus bar cabinet by cable. A typical excitation system cabinet includes an excitation regulator cabinet, an AC switch, multiple power cabinets, an de excitation cabinet, AC / DC bus cabinet, etc. These excitation system cabinets are installed on a 160mm high base (the length and width of the base depend on the number, length and width of the cabinets) in a certain order, so that the excitation system cabinet can be integrated and easy to operate, transportation and power station installation. The outline, internal structure and layout of UNITROL 5000 cabinet are shown in Figure 29-2.

The UNITROL 5000 excitation system is compact in structure. Its functional units are fully modular and standardized according to the rated value and peak value of field current. The intelligent current sharing measures are adopted in the device, and the current sharing coefficient can be increased to more than 0.95 without using the current sharing measures of equal length cables which occupy land and cost. If the rated excitation current is large, it means that a rectifier bridge can be omitted. In addition, the position of AC switch cabinet does not need special design treatment, because it does not need to consider the influence of the connection from secondary winding of rectifier transformer to rectifier bridge on current sharing. Therefore, the AC side of rectifier bridge can adopt standardized bus connection, which simplifies the process. Due to the standardization of design, the procurement and manufacturing of materials become easier and easier, and the production cycle is shorter and shorter.

1.4. working principle

In static excitation system (often called self shunt excitation or machine end excitation), excitation power is taken from generator end. The magnetic field current of synchronous generator is supplied by excitation transformer te, magnetic field breaker Q and thyristor rectifier VZ51-VZ55. The excitation transformer reduces the voltage of generator end to the input voltage required by the excitation system of generator, and provides electrical insulation between generator end and magnetic field winding, and plays the role of rectifier impedance for thyristor rectifier. The thyristor rectifiers VZ51-VZ55 convert the AC current into the controlled DC current If.

When excitation is started, the magnetic field energy is derived from residual voltage at generator end. During the excitation process, the input of thyristor rectifier can work normally only with a voltage of about 10-20v. If the voltage is less than 10-20v, UNITROL 5000 causes the thyristor rectifier to be continuously triggered (diode operating mode) to achieve this value. If the residual voltage at generator end is very low and the residual voltage start excitation fails in a few seconds, the excitation power supply will be automatically put into operation. When the voltage at the machine end reaches 10% of the generator voltage, the excitation power circuit will automatically exit, and the soft excitation process will be started immediately and the voltage will be built to the predetermined voltage level. The whole excitation process and sequence control is realized by AVR software. Because the standby excitation circuit only needs a small current, it can be excited through DC (AC) without impact on the battery power system of the power station.

After grid connection, excitation system can work in AVR mode to adjust the end voltage and reactive power of generator, or it can work in a superposition mode, such as constant power factor regulation, constant reactive power regulation, etc. In addition, it can accept the group regulation instructions of the power plant.

The excitation system device also has protection functions (such as over-voltage and over-current protection) and various limiting functions (such as over excitation, under excitation, voltage / Hz and PSS).

When generator de excitation is needed, the standard solution of UNITROL 5000 excitation system is AC de excitation, which includes magnetic field breaker, thyristor jumper, de excitation resistance and pulse cut-off circuit installed on the AC side of rectifier bridge. If necessary, the magnetic field breaker can also be placed on the DC side of the rectifier bridge. However, this scheme is not generally adopted for the following reasons: firstly, in the case of short circuit in the rectifier, it can reliably disconnect the rectifier from the power supply to prevent the accident from expanding; ② the disconnection from the power side provides a safer guarantee for maintenance and maintenance.

AC de excitation scheme is generally used for generator sets with excitation current less than 4500A. For the larger excitation current, DC de excitation scheme is adopted.

When receiving the excitation protection trip command from generator protection or from the internal, the AC field breaker is disconnected while the pulse is cut off and the thyristor jumper is triggered to turn on the de excitation resistance. Because of the pulse cut-off measures, the AC voltage at the secondary side of the excitation transformer is superimposed on the arc voltage of the magnetic field breaker, which can shorten the time of de excitation.

The design of deexcitation resistance should consider the arc voltage of the magnetic field breaker, the maximum voltage allowed by the excitation winding and the possible maximum de excitation energy in the excitation winding.

Normally shut down, inverter de excitation can be used.

In the past, the excitation system of three units is used more, and now the three machine system is less, so it is not introduced here. Contact the manufacturer if necessary.

1.5. Product series

The commonly used UNITROL 5000 series are as follows:

1.5.1. D5E type  --- single channel  rectifier with one independent controller. This is a minimum configuration UNITROL 5000 system. The main controller, control board (COB), provides all regulation and control functions (including field current regulation function). The manual controller (EGC) tracks the main controller and automatically replaces the main controller when the main controller fails. In this configuration, there is only one thyristor rectifier bridge without redundancy.

1.5.2. D5T type ---  single channel controller with fully redundant dual rectifiers and an independent manual controller. In this configuration, the so-called "dual configuration", two fully redundant rectifiers are used, one of which can be selected as the "on-line" rectifier and the other in the "standby" state. This configuration is usually used for systems with rated output current less than 2000A.

1.5.3. D5S type --- rectifier n-1 configuration, single channel regulator with independent manual controller. In D5S configuration, all rectifier bridges work at the same time. If one of the rectifier bridges fails, the bridge will be cut off automatically, and the rest of the rectifier bridges will undertake the load smoothly. Thyristor rectifier is designed to meet the requirements of the generator in any working condition without any restrictions when a rectifier bridge fails, which is called n-1 configuration.

1.5.4. A5E type --- dual automatic channel controller with single rectifier.

1.5.5. A5T type --- dual automatic channel controller with dual rectifiers.

1.5.6. A5S type ---  rectifier n-1 configuration, dual automatic channel controller.

4.5.7. Q5S type --- rectifier n-1 configuration, dual automatic channel controller, each automatic channel controller with an independent manual controller, equivalent to four channel controller. This configuration has the highest redundancy. The configuration of each regulation channel is also the most complete, including many functions such as independent manual (i.e. field current) regulator.

In the configuration of A5E, A5T and A5S, dual automatic channel controllers are adopted, and each controller can be in "online" or "standby" mode. In addition to the automatic voltage regulation function, each controller also has software functions such as PSS, various restrictions, protection, monitoring and manual control.

 

2. Main technical parameters

The main technical parameters of UNITROL 5000 excitation device are as follows:

2.1. The device can meet the requirements of long-term continuous operation when the excitation voltage and current of the generator do not exceed 1.1 times of its rated value.

2.2. The forced excitation voltage of the device is 2 times of the rated excitation voltage or higher requirements put forward by the user, the multiple of forced excitation current is equal to 2 times of the rated excitation current, and the forced excitation time is not less than 10s.

2.3. The voltage response time is not more than 0.1s.

2.4. The device can make the static error rate of generator voltage less than ± 1%.

2.5. The device adopts reactive power difference to adjust the generator voltage. The range of adjustment rate is ± 15%. The adjustment rate is evenly divided in the whole process.

2.6. When the device is in no load of generator, the step is 5% of the rated voltage of generator, the overshoot is not more than 30% of the step, the number of oscillations is not more than 3 times, the rising time is not more than 0.6s, and the adjustment time is not more than 5S. When the device is under rated load of generator, the step is 2% ~ 4% of the rated voltage of generator, the number of active power fluctuation is not more than 5 times, damping ratio is greater than 0.1, and the adjustment time is not more than 10s.

2.7. The device in excitation control system can meet the requirements of open-loop frequency characteristic gain margin (GM ≥ 6dB), and phase angle margin φ m ≥ 40 °.

2.8. When the generator is raised from zero start, the device can make the maximum voltage of generator not greater than 110% of rated value, the number of oscillations shall not exceed 3 times, and the adjustment time shall not be greater than 10s.

2.9. When the generator is no-load, the device can make the voltage change of generator not more than ± 0.25% of the rated value for every ± 1% of the rated value of the frequency change.

2.10. The current sharing coefficient of power rectifier shall not be less than 0.95.

 

3. Equipment appearance and structure dimension

Due to the different manufacturers of 600MW Generating Units, the excitation parameters are different, so there are several specifications. Here, only one is used to show: see figure 29-3 for the overall dimension, foundation dimension and installation requirements of Q5S-O/U251-S6000.

 

 

4. Selection method

The model can be selected according to the model meaning. However, due to the different generator parameters produced by the main engine manufacturers, the user is generally required to provide the following parameters of generator and the requirements for the device, and the manufacturer shall select the type after calculation.

The parameters of generator provided by the user are as follows:

4.1. Rated capacity of generator SN (MVA) generator rated power PN (MW)

4.2. Rated voltage of generator stator UN (kV) / rated current of generator stator IN (KA).

4.3. Rated excitation voltage of generator rotor UfN (V) / rated excitation current of generator rotor IfN (A)

4.4. Special requirements of users.

 

5. Scope of supply and instructions for ordering

5.1. Scope of supply

5.1.1. See table 29-1 for the supply list.

Table 29-1 supply list (see separate Excel form)

No. Equipment name Model and specification Quantity (unit or piece)
1 AVR cabinet (including impulse signal connection cable) Q5S-O/U251-S6000
A5S-O/U251-S6000
A5S-O/H641-S6000
(the three specifications can be selected according to the excitation parameters of the generator)
1
2 Thyristor rectifier bridge cabinet 5
3 Deexcitation switch cabinet 1
4 Excitation and overvoltage protection cabinet 1
5 AC incoming cabinet 1
6 Excitation voltage transmitter 1
7 Excitation current transmitter 1
8 Rotor one point grounding protection device 1
9 Copper bars connected between cabinets  

 

5.1.2. See table 29-2 for spare parts

Table 29-2 for spare parts, see table 29-2. (see separate Excel table)

No. Name Quantity (piece or unit)
1 Thyristor element 6
2 Fast fuse 6
3 Cooling fan of thyristor rectifier bridge cabinet 2
4 AVR control card 1
5 Trigger pulse board 1
6 Field switch main touch off 1
7 Arc shield 1
8 Opening coil 2
9 Closing coil 2
10 Auxiliary contact of field switch 1
11 Control fuse 1

 

5.1.3. See table 29-3 for special tools

Table 29-3 special tools (see separate Excel table)

Name Model and specification Quantity (unit)
Excitation system debugging tools Ect-tool (including notebook computer, software, optical fiber and interface card) 1

 

5.2. Ordering requirements

The user can roughly select the meaning of the device model according to the requirements of the power plant and the unit. The final order should provide the parameters of generator set to the manufacturer according to the method of type selection. After calculation, the product specification can be determined.