Water cooling stator insulation tester

key word:Heat exchange element


Product description

1. Product name

KD2678 type stator water inner cooling generator insulation characteristic tester

KD2678f water header / engine base equipotential regulator (hereinafter referred to as compensator).

 

2. Generator insulation test method:

2.1. Connect the line according to the requirements: before wiring, make sure that the tester and compensator power switch are in the off position, remove the grounding wire of the steam end and excitation end water header of the 13.7m platform generator, and then short circuit it. Lower the short circuit to the neutral point transformer grounding area of the 6.4m generator in the turbine room, connect the tester water header and the compensator water header socket (black) reliably, Connect the line socket (red) with the pile head on the generator neutral isolation switch; The tester also needs 220 V AC power supply. Please find the power supply nearby and connect the power cord.

2.2. Turn on the power supply of the compensator and turn the selection switch to "LOW". At this time, the LCD will display the interference voltage between the water header and the ground. Press the "TEST / RESET" switch, the indicator will flash, the device is compensating, and the interference voltage will gradually decrease. When the indicator light is on for a long time and the interference voltage is constant (several millivolts to tens of millivolts), the buzzer will sound three times to indicate that the compensation is completed; If the adjustment can not be completed for a long time, the indicator light will flash all the time. After two beeps of the buzzer, turn the selection switch to the "HIGH" gear, and press the "TEST / RESET" switch again to start the adjustment again until the adjustment is completed. Do not turn off the compensator after adjustment.

2.3. Set the function switch of the tester to the "OFF" position, and adjust the mechanical zero adjustment button to make the pointer of the instrument calibrate to the "∞" graduation line of the scale. Then set the function switch to the "2500V" position. At this time, the green power indicator light "power" in the upper left corner of the dial is on, indicating that the power is on. After the safety measures are taken, press the high voltage switch button "HIGH VOLTAGE", then the red high voltage indicator "HV. ON" in the upper right corner of the dial is on, and there is high voltage at the winding end and base end. At the same time, the electric pointer will indicate the insulation resistance value of the tested object on the dial. The tester automatically tests, records the insulation test value in different periods, and calculates it automatically. The applied voltage value is always displayed on the LCD of the tester. The meanings of the six small square buttons above the high voltage switch are: Rt (current insulation resistance value), R15s (15s insulation resistance value), R60s (60s insulation resistance value), r10min (10min insulation resistance value), R60s / R15s (absorption ratio), R60s / R15s (absorption ratio)  R10min / R1min (polarization index value), press the corresponding button to display the value.

2.4. After the test, press the HIGH VOLTAGE switch button "HIGH VOLTAGE" to turn off the high voltage. Set the function switch to "OFF" position and turn off the power. After discharging the residual charge of the generator, remove the test line. After turning off the power, the test data will be lost. Please make relevant records before that. Remove the relevant wiring and put it in place. After removing the short wiring of the water header, the original water header grounding wire must be reliably grounded.